Types of Miniature Circuit Breakers According to IEC 60898-1 Instantaneous Tripping Currents

IEC 60898-1 applies to a.c. air-break circuit-breakers for operation at 50 Hz or 60 Hz, having a rated voltage not exceeding 440 V (between phases), a rated current not exceeding 125 A and a rated short-circuit capacity not exceeding 25 000 A.

Circuit breakers are manufactured in standard sizes, using a system of preferred numbers to cover a range of ratings. Miniature circuit breakers have a fixed trip setting; changing the operating current value requires changing the whole circuit breaker. Larger circuit breakers can have adjustable trip settings, allowing standardized elements to be applied but with a setting intended to improve protection.

Preferred Ratings

For low voltage distribution circuit breakers, International Standards, IEC 60898-1 defines the rated current as the maximum current that the breaker is designed to carry continuously. The commonly available preferred values for the rated current are 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 100 A,and 125 A however, manufacturer have provide current ratings of 1 A, 2 A, and 4 A.

Instantaneous Tripping Currents

The circuit breaker is labeled with the rated current in amperes prefixed by a letter, which indicates the instantaneous tripping current that causes the circuit breaker to trip without intentional time delay expressed in multiples of the rated current:

Types of Miniature Circuit Breakers
Type Instantaneous tripping current Notes
B 3-5 times rated current In For example a 10 A device will trip at 30–50 A. These MCBs are usually used for lighting and smal power loads
C 5 to 10 times In These MCBs are typically used for any types of loads except for motors.
D 10-20 times In These MCBs are usually used for motors and primary protection of transformers due to their in-rush currents.
K 8 to 12 times In

For the protection of loads that cause frequent short duration (approximately 400 ms to 2 s) current peaks in normal operation.

This type of circuit breaker is not covered in IEC 60898-1.

Z 2 to 3 times In for periods in the order of tens of seconds. For the protection of loads such as semiconductor devices or measuring circuits using current transformers. This type of circuit breaker is not covered in IEC 60898-1.
Miniature Circuit Breaker Trip Curve
See also  IEC 61439-1 Minimum Size for PE, PEN Conductors