I. Introduction
This post will present the methodology of MVA Method in performing short circuit calculation. The result will be compared to the Impedance Method of Short-Circuit Calculation and the Per Unit Method later in the article.
The formula used in this example, please refer to Complex MVA Method.
To provide a comparative analysis on the accuracy of each calculation, the example provided in the impedance method will be used in this article just like in the Per Unit Method.
II. Example Calculation
From Figure 1, given the parameters below, calculate the 3-phase fault and X/R ratio at Fault 1, Fault 2 and Fault 3:
- Utility
Available Fault = 436 MVA
X/R = 15 - Cable 1
Length = 1300 m
Unit Resistance = 0.39 ohms/km
Unit Reactance = 0.039 ohms/km
Number of parallel conductors / phase = 1 - Transformer
Primary Voltage = 13.8 kV
Secondary Voltage = 0.48 kV
Capacity = 2 MVA
%Z = 5.75%
X/R = 5.662 - Cable 2
Length = 500 m
Unit Resistance = 0.048 ohms/km
Unit Reactance = 0.029 ohms/km
Number of parallel conductors / phase = 2
Conversion of Actual Values to MVA
- Utility
Available Fault = 436 MVA
X/R = 15
There will be no conversion required for the utility values. The only work here is to break down the MVA into MW and MVAR as
Also, X/R can also be expressed as:
Using eq.1 and eq.2, the MW and MVAR can be calculated.
Notes:
- Use this online tool to to convert or combine complex quantities connected in series or parallel.
- Refer to this article for the formulas used in the succeeding conversions of actual values into MVA values.
- Cable 1
Length = 1300 m
Unit Resistance = 0.39 ohms/km
Unit Reactance = 0.039 ohms/km
Number of parallel conductors / phase = 1- MVA values
- MW2 = 371.902279
- MVAR2 = 37.1902279
- MVA2 = 373.7571647
- Transformer
Primary Voltage = 13.8 kV
Secondary Voltage = 0.48 kV
Capacity = 2 MVA
%Z = 5.75%
X/R = 5.662- MVA values
- MW3 = 6.049538717
- MVAR3 = 34.25248822
- MVA3 = 34.7826087
- Cable 2
Length = 500 m
Unit Resistance = 0.048 ohms/km
Unit Reactance = 0.029 ohms/km
Number of parallel conductors / phase = 2- MVA values
- MW4 = 14.06575517
- MVAR4 = 8.498060413
- MVA4= 16.43357841
III. Fault Calculations
From the above calculated MVA values, it is now possible to calculate the short-circuit currents at the different fault locations. Please note the MVA values in the following calculations is a complex number as represented by eq.1.
Fault 1 (13.8kV)
Calculating the current at Fault1 @ 13.8kV:
The X/R value will be:
Fault 2 (0.48kV)
Calculating the current at Fault2 @ 0.48kV:
The X/R value will be:
Fault 3 (0.48kV)
Calculating the current at Fault3 @ 0.48kV:
The X/R value will be:
IV. Classic MVA Method
The calculation below uses the Classic MVA Method. The MVA value will be a scalar quantity rather than a complex quantity.
Fault 1 (13.8kV)
Calculating the current at Fault1 @ 13.8kV:
Fault 2 (0.48kV)
Calculating the current at Fault2 @ 0.48kV:
Fault 3 (0.48kV)
Calculating the current at Fault3 @ 0.48kV:
V. Impedance Method vs. Per Unit Method vs. MVA Method
The results of the Impedance Method, Per Unit Method and Complex MVA Method are the same hence the accuracy are the same. The Classic MVA Method though has some errors on its results compared to the former.
Comparative Results Fault Impedance Method Per Unit Method Complex MVA Method Classic MVA Method 1 11,005.98 A 11,005.98 A 11,005.98 A 8,419.41 A 2 37,776.15 A 37,776.15 A 37,776.15 A 35,671.55 A 3 13,913.68 A 13,913.68 A 13,913.68 A 12,718.74 A