Circuit breaker rating and type | Opening time at 60 Hz (cycles) | Opening time (seconds) |
---|---|---|
Low voltage (molded case) (< 1000 V) (integral trip) | 1.5 | 0.025 |
Low voltage (insulated case) (< 1000 V) power circuit breaker (integral trip or relay operated) | 3.0 | 0.050 |
Medium voltage (1–35 kV) | 5.0 | 0.080 |
Some high voltage (> 35 kV) | 8.0 | 0.130 |
aThis table does not include the external relay trip times. |
||
Source: IEEE 1584-2002 IEEE Guide for Performing Arc-Flash Hazard Calculations |
Classes of equipment | Typical working distance (mm)a |
---|---|
15 kV switchgear | 910 |
5 kV switchgear | 910 |
Low-voltage switchgear | 610 |
Low-voltage MCCs and panelboards | 455 |
Cable | 455 |
Other | To be determined in field |
a Typical working distance is the sum of the distance between the worker standing in front of the equipment, and from the front of the equipment to the potential arc source inside the equipment. | |
Source: IEEE 1584-2002 IEEE Guide for Performing Arc-Flash Hazard Calculations |
System Voltage (kV) | Type of Equipment | Typical Conductor Gap (mm) | Distance Exponent Factor x |
---|---|---|---|
0.208–1 | Open air | 10–40 | 2.000 |
Switchgear | 32 | 1.473 | |
MCCs and panels | 25 | 1.641 | |
Cables | 13 | 2.000 | |
>1–5 | Open air | 102 | 2.000 |
Switchgear | 13–102 | 0.973 | |
Cables | 13 | 2.000 | |
>5–15 | Open air | 13–153 | 2.000 |
Switchgear | 153 | 0.973 | |
Cables | 13 | 2.000 | |
Source:NFPA 70E® - 2015 Standard for Electrical Safety in the Workplace |
Equipment | Arc Flash PPE Category | Arc-Flash Boundary |
---|---|---|
Panelboards or other equipment rated 240 V and below Parameters: Maximum of 25 kA short-circuit current available; maximum of 0.03 sec (2 cycles) fault clearing time; working distance 455 mm (18 in.) |
1 | 485 mm (19 in.) |
Panelboards or other equipment rated >240 V and up to 600 V
Parameters: Maximum of 25 kA short-circuit current available; maximum of 0.03 sec (2 cycles) fault clearing time; working distance 455 mm (18 in.) |
2 | 900 mm (3 ft) |
Source: NFPA 70E® - 2015 Standard for Electrical Safety in the Workplace |