Philippine Electrical Code 2017 Part 1/Chapter 2. Wiring and Protection/Article 2.80 - Surge Arresters

From Filipino Engineer Wiki
< Philippine Electrical Code 2017 Part 1‎ | Chapter 2. Wiring and Protection
Revision as of 11:07, 6 March 2022 by Admin (talk | contribs) (Created page with "=={{SUBPAGENAME}}== {{Disclaimer PEC}} __TOC__ === 2.80.1 General === ==== 2.80.1.1 Scope. ==== This article covers general requirements, installation requirements, and c...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Article 2.80 - Surge Arresters

DISCLAIMER
This is not an official copy of the Philippine Electrical Code. This is a Design Guide according to the provisions of the Philippine Electrical Code. It also provides interpretation and annotations of the clauses of the Philippine Electrical Code. Any information, interpretation and/or annotation presented herein are based on personal opinion of the authors and does not represent the official interpretation of the Philippine Electrical Code.


While the authors have used good faith and efforts to ensure that the information and instructions contained in this work are accurate, the authors disclaim all responsibility for errors or omissions, including without limitation responsibility for damages resulting from the use of or reliance on this work. Use of the information and instructions contained in this work is at your own risk. If any contents or other technology this work contains or describes is subject to open source licenses or the intellectual property rights of others, it is your responsibility to ensure that your use thereof complies with such licenses and/or rights.

Note: This is a work in progress...

2.80.1 General

2.80.1.1 Scope.

This article covers general requirements, installation requirements, and connection requirements for surge arresters installed on premises wiring systems.

2.80.1.2 Definition.

Surge Arrester. A protective device for limiting surge voltages by discharging or bypassing surge current, and it also prevents continued flow of follow current while remaining capable of repeating these functions.

2.80.1.3 Number Required.

Where used at a point on a circuit, a surge arrester shall be connected to each ungrounded conductor. A single installation of such surge arresters shall be permitted to protect a number of interconnected circuits, provided that no circuit is exposed to surges while disconnected from the surge arresters.

2.80.1.4 Surge Arrester Selection.

(a) Circuits of Less Than 1 000 Volts.

Surge arresters installed on a circuit of less than 1 000 volts shall comply with all of the following:

(1) The rating of the surge arrester shall be equal to or greater than the maximum continuous phase-to-ground power frequency voltage available at the point of application.
(2) Surge arresters installed on circuits of less than 1 000 volts shall be listed.
(3) Surge arresters shall be marked with a short circuit current rating and shall not be installed at a point on the system where the available fault current is in excess of that rating.
(4) Surge arresters shall not be installed on ungrounded systems, impedance grounded systems, or corner grounded delta systems unless listed specifically for use on these systems.
(b) Circuits of 1 kV and Over — Silicon Carbide Types.

The rating of a silicon carbide-type surge arrester shall be not less than 125 percent of the maximum continuous phase-to-ground voltage available at the point of application.

FPN No. 1: For further information on surge arresters, see ANSI/IEEE C62.1-1989, Standard for Gapped Silicon-Carbide Surge Arresters for AC Power Circuits; ANSI/IEEE C62.2-1987, Guide for the Application of Gapped Silicon-Carbide Surge Arresters for Alternating-Current Systems; ANSI/IEEE C62.11-1993, Standard for Metal-Oxide Surge Arresters for Alternating-Current Power Circuits; and ANSI/IEEE C62.22-1991, Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems.

FPN No. 2: The selection of a properly rated metal oxide arrester is based on considerations of maximum continuous operating voltage and the magnitude and duration of overvoltages at the arrester location as affected by phase-to-ground faults, system grounding techniques, switching surges, and other causes. See the manufacturer’s application rules for selection of the specific arrester to be used at a particular location.

2.80.2 Installation

2.80.2.1 Location.

Surge arresters shall be permitted to be located indoors or outdoors. Surge arresters shall be made inaccessible to unqualified persons, unless listed for installation in accessible locations.

2.80.2.2 Routing of Surge Arrester Connections.

The conductor used to connect the surge arrester to line or bus and to ground shall not be any longer than necessary and shall avoid unnecessary bends.

2.80.3 Connecting Surge Arresters

2.80.3.1 Installed at Services of Less Than 1 000 Volts.

Line and ground connecting conductors shall not be smaller than 2.0 mm2 (1.6 mm dia.) copper or 3.5 mm2 (2.0 mm dia.) aluminum. The arrester grounding conductor shall be connected to one of the following:

(1) Grounded service conductor

(2) Grounding electrode conductor

(3) Grounding electrode for the service

(4) Equipment grounding terminal in the service equipment

2.80.3.2 Installed on the Load Side Services of Less Than 1000 Volts.

Line and ground connecting conductors shall not be smaller than 2.0 mm2 (1.6 mm dia.) copper or 3.5 mm2 (2.0 mm dia.) aluminum. A surge arrester shall be permitted to be connected between any two conductors — ungrounded conductor(s), grounded conductor, grounding conductor. The grounded conductor and the grounding conductor shall be interconnected only by the normal operation of the surge arrester during a surge.

2.80.3.3 Circuits of 1 kV and Over — Surge-Arrester Conductors.

The conductor between the surge arrester and the line and the surge arrester and the grounding connection shall not be smaller than 14 mm2 copper or aluminum.

2.80.3.4 Circuits of 1 kV and Over — Interconnections.

The grounding conductor of a surge arrester protecting a transformer that supplies a secondary distribution system shall be interconnected as specified in 2.80.3.4(a), (b), or (c).

(a) Metallic Interconnections.

A metallic interconnection shall be made to the secondary grounded circuit conductor or the secondary circuit grounding conductor provided that, in addition to the direct grounding connection at the surge arrester, the following occurs:

(1) The grounded conductor of the secondary has elsewhere a grounding connection to a continuous metal underground water piping system. However, in urban water-pipe areas where there are at least four water-pipe connections on the neutral and not fewer than four such connections in each mile of neutral, the metallic interconnection shall be permitted to be made to the secondary neutral with omission of the direct grounding connection at the surge arrester.
(2) The grounded conductor of the secondary system is a part of a multiground neutral system or static wire of which the primary neutral or static wire has at least four ground connections in each mile of line in addition to a ground at each service.
(b) Through Spark Gap or Device.

Where the surge arrester grounding conductor is not connected as in 2.80.3.4(a) or where the secondary is not grounded as in 2.80.3.4(a) but is otherwise grounded as in 2.50.3.3, an interconnection shall be made through a spark gap or listed device as follows:

(1) For ungrounded or unigrounded primary systems, the spark gap or listed device shall have a 60-Hz breakdown voltage of at least twice the primary circuit voltage but not necessarily more than 10 kV, and there shall be at least one other ground on the grounded conductor of the secondary that is not less than 6 000 mm distant from the surge arrester grounding electrode.
(2) For multigrounded neutral primary systems, the spark gap or listed device shall have a 60-Hz breakdown of not more than 3 kV, and there shall be at least one other ground on the grounded conductor of the secondary that is not less than 6 000 mm distant from the surge arrester grounding electrode.
(c) By Special Permission.

An interconnection of the surge arrester ground and the secondary neutral, other than as provided in 2.80.3.4(a) or (b), shall be permitted to be made only by special permission.

2.80.3.5 Grounding.

Except as indicated in this article, surge arrester grounding connections shall be made as specified in Article 2.50. Grounding conductors shall not be run in metal enclosures unless bonded to both ends of such enclosure.

Other Pages in this Category: Chapter 2. Wiring and Protection

<DynamicPageList> category = Philippine Electrical Code 2017 Part 1/Chapter 2. Wiring and Protection count = 5 order = ascending addfirstcategorydate = false </DynamicPageList>

References