This article is the first of a series in the selection of electrical cables.
Cable selection is an important part of electrical installation design. Selecting the correct size of cable could lower initial cost, lower operating cost, better voltage regulation notwithstanding the safety factor.
Cable parameters are provided in values per unit length, usually ohms per kilometer(Ω/km) for IEC or miles(Ω/mi) for North American Standards.
The following table illustrate the typical parameters for industrial cables
Nominal conductor area (mm2) |
Single cores in trefoil |
3 cores | Approximate armouring resistance |
||
---|---|---|---|---|---|
Resistance at 90oC (ohm/km) |
Reactance at 50Hz |
Resistance at 90oC (ohm/km) |
Reactance at 50Hz |
GSWB at 60oC 3–4 cores (ohm/km) |
|
1.5 | 15.6 | 0.185 | 15.6 | 0.118 | 46.2 |
2.5 | 9.64 | 0.173 | 9.64 | 0.111 | 51.3 |
4 | 5.99 | 0.163 | 5.99 | 0.108 | 60.3 |
6 | 3.97 | 0.153 | 3.97 | 0.105 | 30.5 |
10 | 2.35 | 0.148 | 2.35 | 0.0983 | 36.7 |
16 | 1.48 | 0.134 | 1.48 | 0.0933 | 23.1 |
25 | 0.936 | 0.125 | 0.936 | 0.0892 | 28.1 |
35 | 0.674 | 0.121 | 0.674 | 0.0867 | 10.43 |
50 | 0.499 | 0.118 | 0.499 | 0.0858 | 11.81 |
70 | 0.344 | 0.112 | 0.344 | 0.0850 | 13.61 |
95 | 0.271 | 0.108 | 0.271 | 0.0825 | 10.87 |
120 | 0.214 | 0.106 | 0.214 | 0.0808 | 11.92 |
150 | 0.175 | 0.105 | 0.175 | 0.0808 | 7.38 |
185 | 0.140 | 0.105 | 0.140 | 0.0808 | 8.15 |
240 | 0.108 | 0.103 | 0.108 | 0.0800 | 8.94 |
300 | 0.087 | 0.101 | 0.087 | 0.0800 | 10.10 |
400 | 0.069 | 0.0992 | 0.069 | 0.0795 | 10.00 |